Freeze Protection
Freeze protection is used to protect the pool and plumbed equipment against freeze damage.
If freeze protection is enabled and the AIR temperature sensor falls below the freeze threshold
(see below), the Aqua Logic will turn on the filter pump to circulate the water. If “Pool and
Spa” is selected in the Pool/Spa sub-menu (see page 24), the valves will also alternate
between the pool and spa every 30 minutes and the filter pump will turn off while the valves
are turning. The chlorinator will not operate if freeze protection is the only reason the pump
is running.
Freeze Protection Temperature
Select the temperature to be used for freeze protection. Temperature is adjustable from 33ºF
- 42ºF (1ºC - 6ºC). 38ºF (3ºC) is default. This threshold will be used for all outputs that have
freeze protection enabled.
NOTE: Heater1 and Heater2 configuration are identical. If Heater2 is enabled then Valve4 will automatically be
disabled due to the fact that they use the same output relay and only 1 function can be assigned to that relay.
Heater1 Config.
+ to view/change
Heater1
Disable
Heater1 Cooldown
Disabled
Heater1 Extend
Disabled
Push to access heater options
Toggle between Enabled and Disabled (default) Heater 1
Toggle between Enabled and Disabled (default) Heater 1 Cooldown
Toggle between Enabled and Disabled (default) Heater 1 Extend
Move to previous/next configuration menu
Move to next menu item or previous/next configuration menu
Move to next menu item
Move to previous/next configuration menu
if “Heater1” is enabled
if “Heater1” is enabled
if “Heater1” is enabled
+
+
>
>
>
>
+
+
+
>
>
>
>
>
>
Heater1 Name
Gas Heater
Rotates between all available names
Move to next menu item
+
>
>
Allow Low Speed
Disabled
Toggle between Enabled and Disabled (default)
Move to
next menu item or previous/next configuration menu
if “Heater1” is enabled and
2-speed filter pump is enabled
Heater1
If the heater is “Enabled”, the heater relay will turn on when the water temperature is less
than the desired temperature setting and the filter pump is running. The desired temperature
is in the “Settings Menu”. If applicable, the homeowner will be prompted to enter separate
“pool” and “spa” settings. Depending on the position of the pool/spa suction valves, the
proper temperature setting will be used.
Heater Name
The Aqua Logic allows you to assign any one of a number of names (e.g. “Gas Heater, Heat
Pump, etc.) to each of the heater control functions. This will make the Aqua Logic much more
user friendly to the homeowner when they want to turn various heaters on or off or set
temperatures. A sheet of small name labels is included with the Aqua Logic main unit and
each remote display/keypad so that appropriate pushbuttons can be labeled the same as the
name that you have assigned.
Heater Cooldown
This feature ensures that the heater cools down before water circulation is stopped. When
enabled, the Aqua Logic will continue to run the filter pump for 5 minutes after the heater
turns off. During this period the filter pump LED will flash and also a “Heater Cooldown,
X:XX remaining” message will scroll on the display.
When the filter pump is running and the heater is on: Pressing the “Filter” button once will
cause the heater to turn off, but the filter pump will continue to run for heater cooldown (filter
LED flashing and message on display). Pushing the filter button a second time will override
the heater cooldown operation and turn the filter pump off.
23
Solar – the lights relay can operate a solar booster pump which will turn on when the filter
pump is running
and solar heat is available and the water is less than the desired temperature
setting. It is important to note that “Solar” must be enabled in the “Solar Config.” menu for
proper operation to occur.
Low Speed of a 2-Speed Spa Filter Pump – the Aqua Logic will turn on the lights relay
whenever the low speed operation of the Dual Equipment Spa filter pump is required. “Pool
and Spa-Dual” (located in Pool/Spa Setup menu) and “2-Speed” (located in Spa Filter Config.
menu) must be selected for proper operation.
Group – the lights relay operates when the Group function is initiated and shuts off when
the Group function is terminated. See Lights Group section for operation information for the
Group function.
Super Chlorinate – The Super Chlorinate function can be assigned to any Aux, Lights or
Valve button. This allows the user to simply hit a button to start a Super Chlorinate cycle,
rather than using the Settings Menu. Note that only one button can me assigned to this
function.
Lights Relay
This feature allows the user to select either “Standard” (default) or “Dimmer” type relay for
the Lights output. The optional AQL-DIM dimmer kit must be installed if “Dimmer” is
desired. When “Dimmer” is selected, and the Lights output is manually turned on, the “+”
and “-” buttons adjust the level from 20% to 100% (default). The level is saved for the next
time the lights are turned from off to on.
Lights Interlock
If enabled, this feature will override the function (Manual On/Off, Countdown Timer,
Timeclock) selected above and turn the lights relay off when: filter pump is off, first 3
minutes of filter pump operation (allows the pump to prime and get water flowing), when the
pool/spa suction return valves are in any position other than “pool only”, or for the first 3
minutes after solar turns on (allows air in the solar panels to be purged). Interlock is not
available for solar, low speed filter pump, dimmer, or group functions.
Lights Group
The Lights Group function allows the user to perform multiple tasks with a single push of the
“Lights” button. When setting up a Group function, refer to page 22 for specific programming
information. There are two Group menus; the first menu determines how the group command
will be initiated (Manual On/Off, Countdown Timer, or Timeclock) and the second menu
selects the desired functions and their respective control parameters.
When activating Group functions, be aware that the most recent Group function that is
initiated will override any previous Group function.
Lights Freeze Protection
This function helps protect equipment that is wired to the lights relay against freeze damage.
If Freeze Protection is enabled and the AIR temperature sensor falls below the selected freeze
temperature threshold, the Aqua Logic will energize the lights relay. IMPORTANT: this only
enables operation of the lights relay during freeze--see the “Filter Pump Config.” menu to
enable freeze protection for the main circulation system. Freeze Protection is not available for
low speed filter pump, dimmer, or group functions.
Spa Filter Config.
+ to view/change
Spa Filter Pump
1 Speed
Freeze Protect
Enabled
Push to access Spa Filter options
Toggle between 1 speed (default) and 2 speed options
Move to previous/next configuration menu item
Move to next menu item
Toggle between Enabled (default) and Disabled Freeze Protection
Move to previous/next configuration menu
+
>
>
+
>
>
+
>
>
if “Pool & Spa Dual” is selected
Spa Filter Pump
For 2-speed pumps: When a 2-speed pump is configured, one of the AUX relays must also
be configured to control the low speed motor winding on the pump (see page 15 for wiring
Page view 22