16
A table of functions and their corresponding control parameters are listed below.
Note that all functions in the table may not be offered. The available functions are dependent on how the
Aqua Logic is configured. For example, if the Aqua Logic is configured for a single heater, “Heater2” will
not be available as an option in the Group menu. Also, under some circumstances, functions will be
displayed but can’t be changed. Note that the function whose menu you are in, will not be displayed as an
option and will automatically turn on when the group is activated. For example, if programming a Group
function under the Lights menu, the Lights function will not be offered as an option and the Lights function
will automatically turn on with the group.
The available control parameters vary with each function. All functions offer “Unaffected”, which should
be selected if you do not wish to control that particular function within the group. All other parameters will
depend on the particular function selected.
When activating Group functions, be aware that the most recent Group function that you activate will
override any previous Group functions.
Heater Setpoints in Groups
The Aqua Logic can be programmed to use alternate heater setpoints (conventional and/or solar) while
running group commands. This allows the heater to be set to a higher or lower temperature than normal,
while the group is activated. When the group stops, the setpoint will return to its normal setting.
Changing the setpoint while the Group is running will make the Group release the alternate setpoint control
and revert back to the normal heater setting. Any changes that are made at that point will affect the normal
heater setting. The next time the Group is activated, the temperature will return to the group setpoint that
was originally programmed in the Configuration Menu. To change the setpoint while the Group is running,
go to the Settings menu and press the +/- button while “Group Control” is displayed. The setpoint will
change and be retained as the new normal heater setpoint.
Pool/Spa Unaffected, Pool only, Spa only, or Spillover
Pool Filter Unaffected, Off, On, High speed, or Low speed
or
Function Control Parameter
Lights Unaffected, Off, or On
Lights Unaffected, Off, On, 100%, 80%, 60%, 40%, or 20%
Spa Filter Unaffected, Off, On, High speed, or Low speed
Aux1-14 Unaffected, Off, On
Aux1-14 Unaffected, Off, On, 100%, 80%, 60%, 40%, or 20%
Valve3 Unaffected, Off, or On
Valve4 Unaffected, Off, or On
Spa Htr1 Set Unaffected, Off, 65º-104ºF
Pool Htr1 Set Unaffected, Off, 65º-104ºF
Spa Htr2 Set Unaffected, Off, 65º-104ºF
Pool Htr2 Set Unaffected, Off, 65º-104ºF
Spa Solar Set Unaffected, Off, 65º-104ºF
Pool Solar Set Unaffected, Off, 65º-104ºF
SuperChlr Unaffected, Off, On
(standard relay)
(dimmer relay)
(s
(dimmer relay)
tandard relay)
27
Countdown Timer – the valve3 relay will turn on when the VALVE3 button is pressed and
then will turn off automatically after a programmed time (see Timers Menu in the Operations
Manual). The VALVE3 button can also be used to turn the output off.
Timeclock – the valve turns on/off at the times set for the valve3 timeclock in the Timers
Menu (see Operations Manual). The valve3 button can also be used to turn the valve output
on or off.
Solar – the valve operates when the filter pump is running
and solar heat is available and the
water is less than the desired temperature setting. Solar heating must be enabled in the
“Solar Config. menu for proper operation to occur.
In-Floor Cleaner – the valve switches the water returning to the pool between the in-floor
cleaner and the normal return jets which facilitate efficient surface skimming. The valve will
operate the in-floor cleaner for the first half of each clock hour and then switch to the jets/
skimming for the last half of the hour.
Group – the valve operates when the Group function is initiated and shuts off when the
Group function is terminated. See valve3 Group section for operation information for the
Group function.
Super Chlorinate – The Super Chlorinate function can be assigned to any Aux, Lights or
Valve button. This allows the user to simply hit a button to start a Super Chlorinate cycle,
rather than using the Settings Menu. Note that only one button can me assigned to this
function.
Valve3 Interlock
If “Enabled”, this feature will override the function (timeclock, manual on/off, countdown
timer or in-floor cleaner) selected above and turn the valve off whenever the filter pump is off
or the pool/spa suction/return valves are set to “spa only” or “spillover” operation. Interlock
is not available with solar or group.
Valve3 Group
The valve3 Group function allows the user to perform multiple tasks with a single push of the
VALVE3 button. When setting up a Group function, refer to page 22 for specific programming
information. There are two Group menus; the first menu determines how the group command
will be initiated (Manual On/Off, Countdown Timer, or Timeclock) and the second menu
selects the desired functions and their respective control parameters.
When activating Group functions, be aware that the most recent Group function that is
initiated will override any previous Group function.
Valve3 Freeze Protection
This function protects the pool and plumbed equipment against freeze damage. If Freeze
Protection is enabled and the AIR temperature falls sensor falls below the selected freeze
protection temperature, the Aqua Logic will turn on the valve to allow circulation of the
water. IMPORTANT: this only enables operation of the valve3 output during freeze--see the
“Filter Pump Config.” menu to enable freeze protection for the main circulation system.
Freeze protection is not available for group functions.